R1233zd Refrigerant Technical Data Sheet
Technical Data Sheet(TDS) trans-1-Chloro-3,3,3-trifluoropropene(HFO-1233zd(E)) CF₃CH=CHCl R1233zd, and.
1 Product Identification
| Item | Value |
|---|---|
| Product Name | R1233zd(E) refrigerant |
| Chemical Name | trans-1-Chloro-3,3,3-trifluoropropene(HFO-1233zd(E)) |
| English Name | trans-1-Chloro-3,3,3-trifluoropropene(HFO-1233zd(E)) |
| Molecular Formula | CF₃CH=CHCl |
| Molecular Weight | 130.50 |
| CAS Registry Number | 102687-65-0 |
| EINECS No. | 688-097-5 |
| UN Number | 3163(per Transport) |
| Transport Hazard Class | Class 2.2, non-flammable gas(per) |
| ASHRAE Safety Classification | A1(Low toxicity, non-flammable) |
| Reference Basis | Manufacturer data; the batch COA governs |
Reference Basis: Compiled from manufacturer data (safety classification per GB/T 7778, ASHRAE 34 / ISO 817)
2 Physical & Chemical Properties
R1233zd Typicaldata, system and,.
| Item | Typical Value |
|---|---|
| Appearance | Colourless transparent liquid (at atmospheric pressure) |
| Odor | Faint, non-irritating |
| Boiling Point (101.3 kPa) | 18.3 ℃ |
| Freezing Point | approx. -107 ℃ |
| Critical Temperature | 165.6 ℃ |
| Critical Pressure | 3.57 MPa |
| Vapor Pressure (25 C, absolute) | approx. 0.128 MPa |
| Liquid Density(25 ℃) | approx. 1270 kg/m³ |
| Saturated Vapor Density(25 ℃) | approx. 6.5 kg/m³ |
| Latent Heat of Vaporization (at boiling point) | approx. 195 kJ/kg |
| Liquid Specific Heat(25 ℃) | approx. 1.26 kJ/(kg K) |
| Vapor Specific Heat(25 ℃, 101.3 kPa) | approx. 0.79 kJ/(kg K) |
| Liquid Thermal Conductivity(25 ℃) | approx. 0.085 W/(m K) |
| Vapor Thermal Conductivity(25 ℃) | approx. 0.0110 W/(m K) |
| Liquid Viscosity(25 ℃) | approx. 0.32 mPa s |
| Vapor Viscosity(25 ℃) | approx. 0.0105 mPa s |
| Surface Tension(25 ℃) | approx. 12.6 mN/m |
| Water Solubility(25 ℃) | Slightly soluble |
| Auto-Ignition Temperature | Not applicable (non-flammable) |
| Flammability Limits in Air (vol.%) | None (non-flammable) |
| OEL (8 h TWA) | 300 ppm |
| Ozone Depletion Potential (ODP) | Low(approx. 0.00034) |
| GWP (100 yr, IPCC AR5) | < 7 |
| Atmospheric Lifetime | approx. 26 |
3 Quality Specifications & Test Methods
R1233zd Parameter, Batch COA.
| Item | Parameter | Test Method |
|---|---|---|
| Appearance | Colourless and clear, free of suspended matter and mechanical impurities | Visual inspection |
| Purity | ≥ 99.80 % | Gas chromatography GC-FID |
| Moisture | ≤ 20 ppm | Karl Fischer coulometric method |
| Acidity( HCl ) | ≤ 0.1 ppm | Alkali absorption - potentiometric titration |
| Evaporation Residue | ≤ 0.01 % | Gravimetric method |
| Non-Condensable Gas(, 25 ℃) | ≤ 1.5 % | Gas chromatography |
| (Z ) | ≤ 0.5 % | Gas chromatography |
| (Cl⁻) | Negative (pass) | Silver nitrate turbidimetry |
4 Comparison with Common Refrigerants
| Comparison Item | R1233zd(this product) | R123 | R245fa |
|---|---|---|---|
| Composition | Single compound HFO-1233zd(E) | Single compound C₂HCl₂F₃ | Single compound C₃H₃F₅ |
| Boiling point | 18.3 ℃ | 27.8 ℃ | 15.3 ℃ |
| ODP | Low(approx. 0.00034) | 0.02 | 0 |
| GWP(100 years, AR5) | < 7 | 77 | 1030 |
| ASHRAE Safety Classification | A1(Non-flammable) | B1(Low) | B1(Low) |
| Vapor Pressure(25 ℃) | approx. 0.128 MPa | approx. 0.092 MPa | approx. 0.148 MPa |
| Atmospheric Lifetime | approx. 26 | approx. 1.3 years | approx. 7.7 years |
| Compatible lubricant | POE | POE / (per) | POE |
| Application | Lowunit and rigid foamfoam blowing | existing installed baseunit servicing | ORC and High temperatureheat pump |
| Current selection | R123 / R245fa low-GWP | controlled, existing installed base servicing | High temperatureheat pump and ORC |
5 Packaging Specifications
| Package Type | Specification | Filling Ratio | Valve Connection | Application |
|---|---|---|---|---|
| / steel drum | 250 kg | Handle as an atmospheric-pressure liquid | Standard drum thread | unitcharging |
| steel cylinder | Made to order( 100 kg / 400 kg) | persteel cylinder | W21.8-14 | Itembulk supply |
| IBC IBC | 1000 kg | Handle as an atmospheric-pressure liquid | IBCconnection | foam blowingsupply |
| ISO ISO tank | approx. 20 t | per ISO tank | ISO tankconnection | and Transport |
Filling Ratioper"", steel cylinderper.
6 Applications
- Lowcentrifugalchiller and air conditioning
- polyurethanerigid foam and blowing agent
- Organic Rankine Cycle(ORC) and waste heat recovery
- High temperatureheat pump and process
Equipment Compatibility & Charging Advice
- R1233zd(E) Low refrigerant(25 ℃ approx. 0.128 MPa), unitnegative pressure, systemtightness and Moisture.
- R123 compressor, and, perdatacharging and.
- A1 Non-flammable refrigerant, OEL 300 ppm, per Occupational exposure limitsventilation and.
- blowing agentperformulation and foam blowingprocess,.
- negative pressureunitpurge recovery unit( purge unit), Non-Condensable Gas.
7 Storage & Transport
- Storage,, ventilation, 40 ℃, ignition source, heat source and.
- Packagingsteel drum / IBC, and.
- Non-flammable refrigerant, Vapour, ventilation Vapour low.
- and oxygen, and (,, ).
- and, enclosed.
- Transportper and Danger, and.
8 Safety & Handling
- Asphyxiation riskVapour, Spillagelow-lying areas, and oxygen, ventilationoxygen(Low 19.5 %).
- Spillageprotective gloves and, enclosed;ventilation,;.
- Thermal decomposition riskopen flames or High temperature,, ventilation.
- —OEL 300 ppm, Vapour, ventilation and, Inhalation and Skin contact.
- and Skin contact15;Skin contact,.
- emissionspercontrolledrecovery, emissions;Disposal.
9 Quality Assurance & Shipping Documents
- Batch COA, Purity( or ), Moisture, Acidity and Evaporation Residue.
- Moisture, and Low temperature.
- 12 months, Batch, No. and.
- perthird-party test report(SGS / ), SDS Description REACH, RoHS.
10 Frequently Asked Questions
R1233zd Can it replace R123 ?
R123 low-GWP Alternatives. R1233zd(E) ODP Low, GWP 7 Non-flammable, and and R123, Lowunit. and charging.
Why is R1233zd unittightness?
R1233zd Low refrigerant, 25 ℃ approx. 0.128 MPa, unitnegative pressure., and Moisture Inhalationsystem,, and, purge recovery unitNon-Condensable Gas.
R1233zd What are its advantages as a blowing agent?
R141b(ODP 0.11, GWP 725) and R245fa(GWP 1030), R1233zd(E) ODP Low, GWP 7, Non-flammable, and, rigid foam low-GWP blowing agent.
R1233zd Shelf life?
Storage, R1233zd(E) Shelf Life 24 months., enclosed.
Specificationdata Typical,;Parameter Batch COA. and, or or, equipment and Regulations.
| Reviewed by: | Approved by: | Hubei Zhongjin Fluorine Chemical Co., Ltd.
Get R1233zd Technical Data Sheet & Quotation
Word Specification and, or Direct Contact sales teamGetBatch Test Report and Quotation.